Parameters
List of Parameters
1-362
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Description: Setting to start the required copy function.
After starting, the corresponding parameters are copied from processor 1 to processor 2.
Once copying is complete, the parameter is automatically reset to zero.
Value: 0: [00 hex] Copy function ended
29: [1D hex] Start copy function node identifier
87: [57 hex] Start copy function SI parameters
208: [D0 hex] Start copy function SI basic parameters
Dependency: Refer to: r3996
Notice: When the parameters are copied, short-term communication interruptions may occur.
Note: Re value = 57 hex and D0 hex:
The value can only be set if the safety commissioning mode is set and the Safety Integrated password was entered.
Re value = D0 hex:
The following parameters are copied after starting the copy function:
p9601 --> p9801, p9610 --> 9810, p9650 --> p9850, p9651 --> p9851
Description: Setting to transfer the reference checksums from the associated actual checksums after changes (SI parameters,
hardware).
After transferring the reference checksums, parameters are automatically reset to zero.
Value: 0: [00 hex] Data unchanged
172: [AC hex] Acknowledge data change complete
220: [DC hex] Acknowledge SI basic parameter change
236: [EC hex] Acknowledge hardware CRC
Dependency: Refer to: r9398, p9399, r9728, p9729, r9798, p9799, r9898, p9899
Note: Re value = AC and DC hex:
These values can only be set if the safety commissioning mode is set and the Safety Integrated password was
entered.
Description: Sets the signal source for the test stop of the safety-relevant motion monitoring functions.
p9700 SI copy function / SI copy function
CU240E-2
CU240E-2 DP
CU240E-2 DP F
CU240E-2 F
Access level: 3 Calculated: - Data type: Integer16
Can be changed: C(95), U, T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0000 hex 00D0 hex 0000 hex
p9701 Acknowledge SI data change / Ackn SI data
CU240E-2
CU240E-2 DP
CU240E-2 DP F
CU240E-2 F
Access level: 3 Calculated: - Data type: Integer16
Can be changed: C(95), U, T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0000 hex 00EC hex 0000 hex
p9705 BI: SI Motion: Test stop signal source / SI Mtn test stop
CU240E-2 DP F
CU240E-2 F
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: C(95) Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - 0