Parameters
List of Parameters
1-34
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Description: Displays supplementary control word.
Note: The following control bits are displayed in r0055:
Bit 00: r1198 Bit 0
Bit 01: r1198 Bit 1
Bit 02: r1198 Bit 2
Bit 03: r1198 Bit 3
Bit 04: r0837 Bit 0
Bit 05: r0837 Bit 1
Bit 08: r2349 Bit 0 (negated)
Bit 09: r1239 Bit 11
Bit 11: r1406 Bit 11
Bit 12: r1406 Bit 12
Bit 13: r2138 Bit 13
Bit 15: r0836 Bit 1
r0055.0...15 CO/BO: Supplementary control word / Suppl STW
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Fixed setp bit 0 Yes No -
01 Fixed setp bit 1 Yes No -
02 Fixed setp bit 2 Yes No -
03 Fixed setp bit 3 Yes No -
04 DDS select. bit 0 Yes No -
05 DDS select. bit 1 Yes No -
08 Technology controller enable Yes No -
09 DC braking enable Yes No -
11 Droop enable Yes No -
12 Torque control active Yes No -
13 External fault 1 (F07860) No Yes -
15 CDS bit 1 Yes No -