Siemens SINAMICS G120 - r1444 Speed controller, speed setpoint steady-state (static); n_ctrl n_set stat; r1445 CO: Actual speed smoothed; n_act smooth; p1452[0...n] Speed controller speed actual value smoothing time (SLVC); n_C n_act T_s SLVC; r1454 CO: Speed controller system deviation I component; n_ctrl sys dev Tn

Siemens SINAMICS G120
750 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of Parameters
Parameters
1-199
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Description: Displays the sum of all speed setpoints that are present.
The following sources are available for the displayed setpoint:
- setpoint at the ramp-function generator input (r1119).
- speed setpoint 1 (p1155).
- speed setpoint 2 (p1160).
- speed setpoint for the speed pre-control (p1430).
- setpoint from DSC (for DSC active).
- setpoint via PC (for master control active).
Dependency: Refer to: r1119, p1155, p1160
Description: Displays the actual smoothed actual speed for speed control.
Description: Sets the smoothing time for the actual speed of the speed controller for encoderless closed-loop speed control.
Note: The smoothing must be increased if there is gear backlash. For longer smoothing times, the integral time of the
speed controller must also be increased (e.g. using p0340 = 4).
Description: Displays the system deviation of the I component of the speed controller.
Description: Sets the source for the adaptation signal to additionally adapt the P gain of the speed controller.
Dependency: Refer to: p1456, p1457, p1458, p1459
r1444 Speed controller, speed setpoint steady-state (static) / n_ctrl n_set stat
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2000 Data set: -
Units group: 3_1 Unit selection: p0505
Min Max Factory setting
- [rpm] - [rpm] - [rpm]
r1445 CO: Actual speed smoothed / n_act smooth
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2000 Data set: -
Units group: 3_1 Unit selection: p0505
Min Max Factory setting
- [rpm] - [rpm] - [rpm]
p1452[0...n] Speed controller speed actual value smoothing time (SLVC) / n_C n_act T_s SLVC
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: - Unit selection: -
Min Max Factory setting
0.00 [ms] 32000.00 [ms] 10.00 [ms]
r1454 CO: Speed controller system deviation I component / n_ctrl sys dev Tn
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2000 Data set: -
Units group: 3_1 Unit selection: p0505
Min Max Factory setting
- [rpm] - [rpm] - [rpm]
p1455[0...n] CI: Speed controller P gain adaptation signal / n_ctrl Adpt_sig Kp
Access level: 4 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: PERCENT Data set: CDS, p0170
Units group: - Unit selection: -
Min Max Factory setting
- - 0