Siemens SINAMICS G120 - p0761[0...1] CU analog inputs wire breakage monitoring response threshold; CU WireBrkThresh; p0762[0...1] CU analog inputs wire breakage monitoring delay time; CU wire brk t_del; p0771[0...1] CI: CU analog outputs signal source; CU AO S_src; r0772[0...1] CU analog outputs, output value currently referred; CU AO outp_val

Siemens SINAMICS G120
750 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of Parameters
Parameters
1-99
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Description: Sets the response threshold for the wire breakage monitoring of the analog inputs.
The unit for the parameter value depends on the set analog input type.
Index: [0] = AI0 (T. 3/4)
[1] = AI1 (T. 10/11)
Dependency: For the following analog input type, the wire breakage monitoring is active:
p0756[0...1] = 1 (unipolar voltage input monitored (+2 V ... +10 V)), unit [V]
p0756[0...1] = 3 (unipolar current input monitored (+4 mA ... +20 mA)), unit [mA]
Refer to: p0756
Note: AI: Analog Input
When p0761 = 0, wire breakage monitoring is not carried out.
Description: Sets the delay time for the wire breakage monitoring of the analog inputs.
Index: [0] = AI0 (T. 3/4)
[1] = AI1 (T. 10/11)
Note: AI: Analog Input
Description: Sets the signal source for the analog outputs.
Index: [0] = AO0 (T 12/13)
[1] = AO1 (T 26/27)
Note: AO: Analog Output
T: Terminal
Description: Displays the actual referred output value of the analog outputs.
Index: [0] = AO0 (T 12/13)
[1] = AO1 (T 26/27)
Note: AO: Analog Output
T: Terminal
p0761[0...1] CU analog inputs wire breakage monitoring response threshold / CU WireBrkThresh
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0.00 20.00 2.00
p0762[0...1] CU analog inputs wire breakage monitoring delay time / CU wire brk t_del
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: U, T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0 [ms] 1000 [ms] 100 [ms]
p0771[0...1] CI: CU analog outputs signal source / CU AO S_src
Access level: 2 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: U, T Scaling: PERCENT Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - [0] 21[0]
[1] 27[0]
r0772[0...1] CU analog outputs, output value currently referred / CU AO outp_val
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- [%] - [%] - [%]

Table of Contents