Description: Runs the corresponding macro files.
The selected macro file must be available on the memory card/device memory.
Example:
p0015 = 6 --> the macro file PM000006.ACX is run.
Dependency: Refer to: p0700, p1000, p1500, r8570
Caution: When executing a specific macro, the corresponding programmed settings are made and become active.
Notice: After the value has been modified, no further parameter modifications can be made and the status is shown in
r3996. Modifications can be made again when r3996 = 0.
Note: The macros in the specified directory are displayed in r8570. r8570 is not in the expert list of the commissioning
software.
Macros available as standard are described in the technical documentation of the particular product.
The parameter is not influenced by setting the factory setting.
Description: Displays the firmware version of the Control Unit.
Dependency: Refer to: r0197, r0198
Note: Example:
The value 1010100 should be interpreted as V01.01.01.00.
Description: Displays the currently smoothed speed setpoint at the input of the speed controller or U/f characteristic (after the
interpolator).
Dependency: Refer to: r0060
Note: Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The speed setpoint is available smoothed (r0020) and unsmoothed (r0060).
p0015 Macro drive unit / Macro drv unit
CU240B-2 DP
CU240E-2 DP
CU240E-2 DP F
Access level: 1 Calculated: - Data type: Unsigned32
Can be changed: C, C(1) Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0 999999 7
r0018 Control Unit Firmware-Version / CU FW version
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0 4294967295 -
r0020 Speed setpoint smoothed / n_set smth
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2000 Data set: -
Units group: 3_1 Unit selection: p0505
Min Max Factory setting
- [rpm] - [rpm] - [rpm]