Parameters
List of Parameters
1-280
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Description: Sets the acknowledge mode for selected fault.
Value: 1: Acknowledgment only using POWER ON
2: Ack IMMEDIATELY after the fault cause has been removed
Dependency: Selects the faults and sets the required acknowledge mode realized under the same index
Refer to: p2126
Notice: It is not possible to re-parameterize the acknowledge mode of a fault in the following cases:
- if there is no existing fault number.
- the message type is not "fault" (F).
- when a fault is present.
Note: The acknowledge mode can only be changed for faults with the appropriate identification.
Example:
F12345 and acknowledge mode = IMMEDIATE (POWER ON)
--> The acknowledge mode can be changed from IMMEDIATELY to POWER ON.
Description: Selects faults or alarms which can be used as trigger.
Dependency: Refer to: r2129
Description: Trigger signal for the selected faults and alarms
Dependency: If one of the faults or alarms selected in p2128[n] occurs, then the particular bit of this binector output is set.
Refer to: p2128
Note: CO: r2129 = 0 --> None of the selected messages has occurred.
CO: r2129 > 0 --> At least one of the selected messages has occurred.
p2127[0...19] Sets acknowledgement mode / Acknowledge mode
Access level: 3 Calculated: - Data type: Integer16
Can be changed: U, T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
1 2 1
p2128[0...15] Selecting fault/alarm code for trigger / Message trigger
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: U, T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0 65535 0
r2129.0...15 CO/BO: Trigger word for faults and alarms / Trigger word
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Trigger signal p2128[0] ON OFF -
01 Trigger signal p2128[1] ON OFF -
02 Trigger signal p2128[2] ON OFF -
03 Trigger signal p2128[3] ON OFF -
04 Trigger signal p2128[4] ON OFF -
05 Trigger signal p2128[5] ON OFF -
06 Trigger signal p2128[6] ON OFF -
07 Trigger signal p2128[7] ON OFF -
08 Trigger signal p2128[8] ON OFF -
09 Trigger signal p2128[9] ON OFF -
10 Trigger signal p2128[10] ON OFF -
11 Trigger signal p2128[11] ON OFF -
12 Trigger signal p2128[12] ON OFF -
13 Trigger signal p2128[13] ON OFF -
14 Trigger signal p2128[14] ON OFF -
15 Trigger signal p2128[15] ON OFF -