EasyManua.ls Logo

Siemens SINAMICS G120 - p3322[0...n] Fluid flow machine P = f(n), Y coordinate: P flow2 %, point 2; Fluid flow mach Y2; p3323[0...n] Fluid flow machine P = f(n), X coordinate: n flow2 %, point 2; Fluid flow mach X2; p3324[0...n] Fluid flow machine P = f(n), Y coordinate: P flow3 %, point 3; Fluid flow mach Y3; p3325[0...n] Fluid flow machine P = f(n), X coordinate: n flow3 %, point 3; Fluid flow mach X3

Siemens SINAMICS G120
750 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters
List of Parameters
1-320
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Description: The power (P) for point 2 on the Y coordinate of the flow characteristic is saved in p3322. Unit: %
Dependency: Refer to: p3323
Note: The reference value for power and speed is the rated power/rated speed.
The energy saved is displayed in r0041.
Description: The speed (n) for point 2 on the X coordinate of the flow characteristic is saved in p3323. Unit: %
Dependency: Refer to: p3322
Note: The reference value for power and speed is the rated power/rated speed.
The energy saved is displayed in r0041.
Description: The power (P) for point 3 on the Y coordinate of the flow characteristic is saved in p3324. Unit: %
Dependency: Refer to: p3325
Note: The reference value for power and speed is the rated power/rated speed.
The energy saved is displayed in r0041.
Description: The speed (n) for point 3 on the X coordinate of the flow characteristic is saved in p3325. Unit: %
Dependency: Refer to: p3324
Note: The reference value for power and speed is the rated power/rated speed.
The energy saved is displayed in r0041.
p3322[0...n] Fluid flow machine P = f(n), Y coordinate: P flow2 %, point 2 / Fluid flow mach Y2
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: - Unit selection: -
Min Max Factory setting
0.00 100.00 50.00
p3323[0...n] Fluid flow machine P = f(n), X coordinate: n flow2 %, point 2 / Fluid flow mach X2
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: - Unit selection: -
Min Max Factory setting
0.00 100.00 25.00
p3324[0...n] Fluid flow machine P = f(n), Y coordinate: P flow3 %, point 3 / Fluid flow mach Y3
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: - Unit selection: -
Min Max Factory setting
0.00 100.00 77.00
p3325[0...n] Fluid flow machine P = f(n), X coordinate: n flow3 %, point 3 / Fluid flow mach X3
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: - Unit selection: -
Min Max Factory setting
0.00 100.00 50.00