SINAMICS G120 Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Description: Sets the load monitoring configuration.
Value: 0: Monitoring switched out
1: Monitoring torque and load drop
2: Monitoring speed and load drop
3: Monitoring load drop
Dependency: Refer to: p2182, p2183, p2184, p2185, p2186, p2187, p2188, p2189, p2190, p2192, r2198, p3230, p3231, p3232
Refer to: A07920, A07921, A07922, F07923, F07924, F07925, F07936
Description: Sets the torque threshold value for the message "Torque utilization < torque threshold value 2" (BO: r2199.11).
The message "torque setpoint < p2174" (BO: r2198.10) and "torque utilization < p2194" (BO: r2199.11) are only
evaluated after the run-up and the delay time has expired.
Dependency: Refer to: r0033, p2195, r2199
Description: Sets the switch-off delay time for the negated signal "run-up completed".
The message "torque setpoint < p2174" (BO: r2198.10) and "torque utilization < p2194" (BO: r2199.11) are only
evaluated after the run-up and the delay time has expired.
Dependency: Refer to: p2174, p2194
Description: Sets the scaling factor for torque utilization (r0033).
p2193[0...n] Load monitoring configuration / Load monit config
Access level: 3 Calculated: - Data type: Integer16
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: - Unit selection: -
Min Max Factory setting
0 3 1
p2194[0...n] Torque threshold value 2 / M_thresh val 2
Access level: 3 Calculated: p0340 = 1,3,5 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: - Unit selection: -
Min Max Factory setting
0.00 [%] 100.00 [%] 90.00 [%]
p2195[0...n] Torque utilization switch-off delay / M_util t_off
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: - Unit selection: -
Min Max Factory setting
0.0 [ms] 1000.0 [ms] 800.0 [ms]
p2196[0...n] Torque utilization scaling / M_util scal
Access level: 1 Calculated: - Data type: FloatingPoint32
Can be changed: C(1, 3), U, T Scaling: - Data set: DDS, p0180
Units group: - Unit selection: -
Min Max Factory setting
0.00 [%] 1000.00 [%] 100.00 [%]