Siemens SINAMICS G120 - p0757[0...1] CU analog inputs characteristic value x1; CU AI char x1; p0758[0...1] CU analog inputs characteristic value y1; CU AI char y1; p0759[0...1] CU analog inputs characteristic value x2; CU AI char x2; p0760[0...1] CU analog inputs characteristic value y2; CU AI char y2

Siemens SINAMICS G120
750 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters
List of Parameters
1-98
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Description: Sets the scaling characteristic for the analog inputs.
The scaling characteristic for the analog inputs is defined using 2 points.
This parameter specifies the x coordinate (V, mA) of the 1st value pair of the characteristic.
Index: [0] = AI0 (T. 3/4)
[1] = AI1 (T. 10/11)
Note: The parameters for the characteristic do not have a limiting effect.
Description: Sets the scaling characteristic for the analog inputs.
The scaling characteristic for the analog inputs is defined using 2 points.
This parameter specifies the y coordinate (percentage) of the 1st value pair of the characteristic.
Index: [0] = AI0 (T. 3/4)
[1] = AI1 (T. 10/11)
Note: The parameters for the characteristic do not have a limiting effect.
Description: Sets the scaling characteristic for the analog inputs.
The scaling characteristic for the analog inputs is defined using 2 points.
This parameter specifies the x coordinate (V, mA) of the 2nd value pair of the characteristic.
Index: [0] = AI0 (T. 3/4)
[1] = AI1 (T. 10/11)
Note: The parameters for the characteristic do not have a limiting effect.
Description: Sets the scaling characteristic for the analog inputs.
The scaling characteristic for the analog inputs is defined using 2 points.
This parameter specifies the y coordinate (percentage) of the 2nd value pair of the characteristic.
Index: [0] = AI0 (T. 3/4)
[1] = AI1 (T. 10/11)
Note: The parameters for the characteristic do not have a limiting effect.
p0757[0...1] CU analog inputs characteristic value x1 / CU AI char x1
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
-50.000 160.000 0.000
p0758[0...1] CU analog inputs characteristic value y1 / CU AI char y1
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
-1000.00 [%] 1000.00 [%] 0.00 [%]
p0759[0...1] CU analog inputs characteristic value x2 / CU AI char x2
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
-50.000 160.000 10.000
p0760[0...1] CU analog inputs characteristic value y2 / CU AI char y2
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
-1000.00 [%] 1000.00 [%] 100.00 [%]