List of Parameters
Parameters
1-145
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Description: Sets the signal source for jog 2.
Dependency: Refer to: p0840, p1059
Notice: The drive is enabled for jogging using BI: p1055 or BI: p1056.
The command "ON/OFF1" can be issued using BI: p0840 or using BI: p1055/p1056.
Only the signal source that was used to power up can also be used to power down again.
Description: Sets the speed/velocity for jog 1. Jogging is level-triggered and allows the motor to be incrementally moved.
Dependency: Refer to: p1055, p1056
Description: Sets the speed/velocity for jog 2. Jogging is level-triggered and allows the motor to be incrementally moved.
Dependency: Refer to: p1055, p1056
Description: Sets the speed limit/velocity limit effective in the setpoint channel.
Dependency: Refer to: p1082, p1083, p1085, p1086, p1088
p1056[0...n] BI: Jog bit 1 / Jog bit 1
CU240B-2 DP
CU240E-2 DP
CU240E-2 DP F
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Data set: CDS, p0170
Units group: - Unit selection: -
Min Max Factory setting
- - [0] 0
[1] 722.1
[2] 0
[3] 0
p1058[0...n] Jog 1 speed setpoint / Jog 1 n_set
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T Scaling: - Data set: DDS, p0180
Units group: 3_1 Unit selection: p0505
Min Max Factory setting
-210000.000 [rpm] 210000.000 [rpm] 150.000 [rpm]
p1059[0...n] Jog 2 speed setpoint / Jog 2 n_set
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T Scaling: - Data set: DDS, p0180
Units group: 3_1 Unit selection: p0505
Min Max Factory setting
-210000.000 [rpm] 210000.000 [rpm] -150.000 [rpm]
p1063[0...n] Speed limit setpoint channel / n_limit setp
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: 3_1 Unit selection: p0505
Min Max Factory setting
0.000 [rpm] 210000.000 [rpm] 210000.000 [rpm]