Parameters
List of Parameters
1-72
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Description: Displays the actual stator resistance (phase value).
The parameter value also contains the temperature-independent cable resistance.
Dependency: In the case of induction motors the parameter is also affected by the motor temperature model.
Refer to: p0350, p0352, p0620
Note: In each case, only the stator resistance of the active Motor Data Set is included with the stator temperature of the
thermal motor model.
Description: Displays the actual rotor resistance (phase value).
The parameter is affected by the motor temperature model.
Dependency: Refer to: p0354, p0620
Note: In each case, only the rotor resistance of the active Motor Data Set is included with the rotor temperature of the
thermal motor model.
This parameter is not used for synchronous motors (p0300 = 2xx).
Description: Setting to invert the digital input signals to connect a measuring probe.
Dependency: Refer to: p0580
Note: When the measuring probe is inverted, this has no effect on the status displays of the digital inputs (r0721, r0722,
r0723).
r0395[0...n] Actual stator resistance / R_stator act
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Data set: MDS
Units group: - Unit selection: -
Min Max Factory setting
- [ohm] - [ohm] - [ohm]
r0396[0...n] Actual rotor resistance / R_rotor act
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Data set: MDS
Units group: - Unit selection: -
Min Max Factory setting
- [ohm] - [ohm] - [ohm]
p0490 Meas. probe invert / Probe inv
CU240E-2
CU240E-2 DP
CU240E-2 DP F
CU240E-2 F
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: U, T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
03 DI 3 (T. 8) Inverted Not inverted -