List of Parameters
Parameters
1-167
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Description: Displays the status for checking and monitoring flying restart states in the vector control mode.
Note: Re bit 00 ... 09:
Used to control internal sequences during the flying restart.
Depending on the motor type (p0300), the number of active bits differs.
Re bits 10 ... 15:
Are used to monitor the flying restart sequence.
For permanent-magnet synchronous motors (PEM) only bits 10, 11 and 15 are supported.
Description: Selects the faults for which automatic restart should not be effective.
Dependency: The setting is only effective for p1210 = 6, 16.
Refer to: p1210
r1205.0...15 CO/BO: Flying restart, vector control status / FlyRest vector st
Access level: 4 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Speed adaptation circuit record angle Yes No -
01 Speed adaptation circuit set gain to 0 Yes No -
02 Isd channel enable Yes No -
03 Speed control switched out Yes No -
04 Quadrature arm switched in Yes No -
05 Special transformation active Yes No -
06 Speed adaptation circuit set I comp to 0 Yes No -
07 Current control on Yes No -
08 Isd_set = 0 A Yes No -
09 Frequency held Yes No -
10 Search in the positive direction Yes No -
11 Search Started Yes No -
12 Current impressed Yes No -
13 Search interrupted Yes No -
14 Speed adaptation circuit deviation = 0 Yes No -
15 Speed control activated Yes No -
p1206[0...9] Set the fault number without automatic restart / Fault_No w/o AR
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: U, T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0 65535 0