EasyManua.ls Logo

Siemens SINAMICS G120 - r1527 CO: Torque limit lower without offset; M_max low w;o offs; p1528[0...n] CI: Torque limit upper scaling; M_max upper scal; p1529[0...n] CI: Torque limit lower scaling; M_max lower scal; p1530[0...n] Power limit motoring; P_max mot

Siemens SINAMICS G120
750 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters
List of Parameters
1-214
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Description: Displays the lower torque limit of all torque limits without offset.
Dependency: Refer to: p1520, p1521, p1522, p1523, p1528, p1529
Description: Sets the signal source for the scaling of the upper torque limit in p1522.
Danger: For p1400.4 = 0 (torque limiting, upper/lower) the following applies:
Negative values resulting from the signal source and scaling can cause the motor to accelerate in an uncontrolled
manner.
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description: Sets the signal source for the scaling of the lower torque limit in p1523.
Danger: For p1400.4 = 0 (torque limiting, upper/lower) the following applies:
Positive values resulting from the signal source and scaling can cause the motor to accelerate in an uncontrolled
manner.
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description: Sets the power limit when motoring.
Dependency: Refer to: p0500, p1531
Note: The power limit is limited to 300% of the rated motor power.
r1527 CO: Torque limit lower without offset / M_max low w/o offs
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2003 Data set: -
Units group: 7_1 Unit selection: p0505
Min Max Factory setting
- [Nm] - [Nm] - [Nm]
p1528[0...n] CI: Torque limit upper scaling / M_max upper scal
Access level: 4 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: PERCENT Data set: CDS, p0170
Units group: - Unit selection: -
Min Max Factory setting
- - 1524[0]
p1529[0...n] CI: Torque limit lower scaling / M_max lower scal
Access level: 4 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: PERCENT Data set: CDS, p0170
Units group: - Unit selection: -
Min Max Factory setting
- - 1525[0]
p1530[0...n] Power limit motoring / P_max mot
Access level: 2 Calculated: p0340 = 1,3,5 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: 14_5 Unit selection: p0505
Min Max Factory setting
0.00 [kW] 100000.00 [kW] 0.00 [kW]