Siemens SINAMICS G120 - p0634[0...n] Q flux flux constant unsaturated; PSIQ KPSI UNSAT; p0635[0...n] Q flux quadrature axis current constant unsaturated; PSIQ KIQ UNSAT; p0636[0...n] Q flux direct axis current constant unsaturated; PSIQ KID UNSAT; p0637[0...n] Q flux flux gradient saturated; PSIQ Grad SAT

Siemens SINAMICS G120
750 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters
List of Parameters
1-86
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Description: The non-linear and cross-coupled quadrature axis flux functions are defined using 4 coefficients.
The parameter weights the unsaturated component of the quadrature axis flux function.
Description: The non-linear and cross-coupled quadrature axis flux functions are defined using 4 coefficients.
This parameter describes the interdependency of the unsaturated component of the quadrature axis current.
Dependency: Refer to: p0634
Description: The non-linear and cross-coupled quadrature axis flux functions are defined using 4 coefficients.
This parameter describes the interdependency of the unsaturated component of the direct axis current.
Dependency: Refer to: p0634
Description: The non-linear and cross-coupled quadrature axis flux functions are defined using 4 coefficients.
This parameter describes the gradients of the saturated component over the quadrature axis current.
Dependency: Refer to: p0634, p0635, p0636
p0634[0...n] Q flux flux constant unsaturated / PSIQ KPSI UNSAT
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: C(3), U, T Scaling: - Data set: MDS
Units group: - Unit selection: -
Min Max Factory setting
0.000 [Vsrms] 100.000 [Vsrms] 0.000 [Vsrms]
p0635[0...n] Q flux quadrature axis current constant unsaturated / PSIQ KIQ UNSAT
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: C(3), U, T Scaling: - Data set: MDS
Units group: - Unit selection: -
Min Max Factory setting
0.00 [Arms] 10000.00 [Arms] 0.00 [Arms]
p0636[0...n] Q flux direct axis current constant unsaturated / PSIQ KID UNSAT
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: C(3), U, T Scaling: - Data set: MDS
Units group: - Unit selection: -
Min Max Factory setting
0.00 [Arms] 10000.00 [Arms] 0.00 [Arms]
p0637[0...n] Q flux flux gradient saturated / PSIQ Grad SAT
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: C(3), U, T Scaling: - Data set: MDS
Units group: - Unit selection: -
Min Max Factory setting
0.00 [mH] 10000.00 [mH] 0.00 [mH]