Parameters
List of Parameters
1-294
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Description: Sets the speed/torque envelope curve for load monitoring.
Dependency: The following applies: p2188 < p2187
Refer to: p2183, p2187
Note: The lower envelope curve is defined by p2186, p2188 and p2190.
Description: Sets the speed/torque envelope curve for load monitoring.
Dependency: The following applies: p2189 > p2190
Refer to: p2184, p2190
Note: The upper envelope curve is defined by p2185, p2187 and p2189.
Description: Sets the speed/torque envelope curve for load monitoring.
Dependency: The following applies: p2190 < p2189
Refer to: p2184, p2189
Note: The lower envelope curve is defined by p2186, p2188 and p2190.
Description: Sets the delay time to evaluate the load monitoring.
p2188[0...n] Load monitoring torque threshold 2, lower / M_thresh 2 lower
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: 7_1 Unit selection: p0505
Min Max Factory setting
0.00 [Nm] 20000000.00 [Nm] 0.00 [Nm]
p2189[0...n] Load monitoring torque threshold 3, upper / M_thresh 3 upper
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: 7_1 Unit selection: p0505
Min Max Factory setting
0.00 [Nm] 20000000.00 [Nm] 10000000.00 [Nm]
p2190[0...n] Load monitoring torque threshold 3, lower / M_thresh 3 lower
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: 7_1 Unit selection: p0505
Min Max Factory setting
0.00 [Nm] 20000000.00 [Nm] 0.00 [Nm]
p2192[0...n] Load monitoring delay time / Load monit t_del
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: - Unit selection: -
Min Max Factory setting
0.00 [s] 65.00 [s] 10.00 [s]