Siemens SINAMICS G120 - p2268 Technology controller lower limit actual value; Tec_ctrl l_lim act; p2269 Technology controller gain actual value; Tech_ctrl gain act; p2270 Technology controller actual value function; Tec_ctr ActVal fct; p2271 Technology controller actual value inversion (sensor type); Tech_ctrl act inv

Siemens SINAMICS G120
750 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of Parameters
Parameters
1-309
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Description: Sets the lower limit for the actual value signal of the technology controller.
Dependency: Refer to: p2264, p2265, p2271
Refer to: F07426
Notice: If the actual value falls below this lower limit, this results in fault F07426.
Description: Scaling factor for the actual value of the technology controller.
Dependency: Refer to: p2264, p2265, p2267, p2268, p2271
Note: For 100%, the actual value is not changed.
Description: Setting to use an arithmetic function for the actual value signal of the technology controller.
Value: 0: No function
1: Root function (root from x)
2: Square function (x * x)
3: Cube function (x * x * x)
Dependency: Refer to: p2264, p2265, p2267, p2268, p2269, p2271
Description: Setting to invert the actual value signal of the technology controller.
The inversion depends on the sensor type for the actual value signal.
Value: 0: No inversion
1: Inversion actual value signal
Caution: If the actual value inversion is incorrectly selected, then the closed-loop control with the technology controller can
become unstable and can oscillate!
Note: The correct setting can be determined as follows:
- inhibit the technology controller (p2200 = 0).
- increase the motor speed and in so doing, measure the actual value signal of the technology controller.
--> If the actual value increases as the motor speed increases, then p2271 should be set to 0 (no inversion).
--> If the actual value decreases as the motor speed increases, then p2271 should be set to 1 (the actual value sig-
nal is inverted).
p2268 Technology controller lower limit actual value / Tec_ctrl l_lim act
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Data set: -
Units group: 9_1 Unit selection: p0595
Min Max Factory setting
-200.00 [%] 200.00 [%] -100.00 [%]
p2269 Technology controller gain actual value / Tech_ctrl gain act
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0.00 [%] 500.00 [%] 100.00 [%]
p2270 Technology controller actual value function / Tec_ctr ActVal fct
Access level: 3 Calculated: - Data type: Integer16
Can be changed: U, T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0 3 0
p2271 Technology controller actual value inversion (sensor type) / Tech_ctrl act inv
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0 1 0