Parameters
List of Parameters
1-284
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Description: Sets the hysteresis speed (bandwidth) for the signal "f or n / v comparison value reached or exceeded" (BO:
r2199.1).
Dependency: Refer to: p2141, r2199
Description: Sets the signal source for the negated enable (0 = enable) of the motor stall monitoring.
Dependency: Refer to: p2163, p2164, p2166, r2197, r2198
Refer to: F07900
Note: If the enable signal is connected to r2197.7 then the stall signal is suppressed if there is no speed setpoint - actual
value deviation.
Description: Displays the system runtime in days when the alarm occurred.
Dependency: Refer to: r2110, r2122, r2123, r2124, r2125, r2134, r2146
Notice: The time comprises r2145 (days) and r2123 (milliseconds).
Note: The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
Description: Displays the system runtime in days when the alarm was cleared.
Dependency: Refer to: r2110, r2122, r2123, r2124, r2125, r2134, r2145
Notice: The time comprises r2146 (days) and r2125 (milliseconds).
Note: The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
p2142[0...n] Hysteresis speed 1 / n_hysteresis 1
Access level: 3 Calculated: p0340 = 1,3,5 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: 3_1 Unit selection: p0505
Min Max Factory setting
0.00 [rpm] 300.00 [rpm] 2.00 [rpm]
p2144[0...n] BI: Motor stall monitoring enable (negated) / Mot stall enab neg
Access level: 4 Calculated: - Data type: U32 / Binary
Can be changed: U, T Scaling: - Data set: CDS, p0170
Units group: - Unit selection: -
Min Max Factory setting
- - 0
r2145[0...63] Alarm time received in days / t_alarm recv days
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - -
r2146[0...63] Alarm time removed in days / t_alarm res days
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - -