List of Parameters
Parameters
1-297
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Description: Displays the second status word for monitoring functions.
Note: Re bit 10:
The torque threshold value 1 is set in p2174.
Re bit 12:
This bit is reset after the fault cause disappears, even if the fault itself is still present.
Description: Displays the third status word for monitoring functions.
Note: Re bit 00:
The speed threshold value 3 is set in p2161.
Re bit 01:
The comparison value is set in p2141. We recommend setting the hysteresis (p2142) for canceling the bit to a value
lower than that in p2141. Otherwise, the bit will never be reset.
Re bit 11:
The torque threshold value 2 is set in p2194.
r2198.0...13 CO/BO: Status word monitoring 2 / ZSW monitor 2
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 |n_act| <= speed threshold value 5 Yes No 8021
01 |n_act| > speed threshold value 5 Yes No 8021
02 |n_act| <= speed threshold value 6 Yes No 8021
03 |n_act| > speed threshold value 6 Yes No 8021
04 |n_set| < p2161 Yes No 8011
05 n_set > 0 Yes No 8011
06 Motor blocked Yes No 8012
07 Motor stalled Yes No 8012
08 |I_act| < I_threshold value p2170 Yes No 8020
09 |M_act| > torque threshold value 1 and
n_set reached
Yes No 8021
10 |M_set| < torque threshold value 1 Yes No 8012
11 Load monitoring signals an alarm Yes No 8013
12 Load monitoring signals a fault condition Yes No 8013
13 |M_act| > torque threshold value 1 Yes No 8021
r2199.0...11 CO/BO: Status word monitoring 3 / ZSW monitor 3
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 |n_act| < speed threshold value 3 Yes No 8010
01 f or n comparison value reached or
exceeded
Yes No 8010
04 Speed setp - act val deviation in tolerance
t_on
Yes No 8011
05 Ramp-up/ramp-down completed Yes No 8011
11 Torque utilization < torque threshold value 2 Yes No 8012