EasyManua.ls Logo

Siemens SINAMICS G120 - Fig. 2-29 2420 - Telegrams and Process Data (PZD)

Siemens SINAMICS G120
750 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Communication
Function diagrams
2-527
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Fig. 2-29 2420 – Telegrams and Process Data (PZD)
- 2420 -
Function diagram
87654321
FP_2420_97_61.vsd
PROFIdrive / PROFIBUS
G120 CU240B/E-2 DP
13.12.2010 V4.4
Telegrams and Process Data (PZD)
<1>
<2>
If p0922 = 999 is changed to another value, the telegram is automatically assigned.
If p0922 unequal 999 is changed to p0922 = 999, the "old" telegram assignment is maintained!
Freely interconnectable (pre-setting: MELD_NAMUR).
<1>
1 20
PZD6
PZD5
PZD4
PZD1
PZD2
PZD3
STW1 ZSW1
NSOLL_A NIST_A
STW1 ZSW1
MIST_GL
PIST_GL
<2>
NIST_A_GL
IAIST_GL
NSOLL_A
PD Telegr_sel
1 ... 999
p0922 (1)
Interconnec-
tion is made
according to
Telegram
[2440] [2450] automatically
PZD8
PZD7
350
STW1 ZSW1
ZSW3
NIST_A_GL
IAIST_GL
NSOLL_A
STW3
M_LIM
<3>
Can be freely connected.
999
STW1 <4> ZSW1 <4>
Receive telegram length
freely selectable via
central PROFIdrive
configuration in the
master
Transmit telegram
length freely selectable
via central PROFIdrive
configuration in the
master
<4>
In order to comply with the PROFIdrive profile, PZD1 must be used as control word 1 (STW1) or status word 1 (ZSW1).
p2037 = 2 should be set if STW1 is not transferred with PZD1 as specified in the PROFIdrive profile.
Receive telegram from
PROFIdrive
Send telegram to
PROFIdrive
352
STW1 ZSW1
MIST_GL
WARN_CODE
FAULT_CODE
NIST_A_GL
IAIST_GL
NSOLL_A
<3>
<3>
<3>
<3>
353
STW1 ZSW1
NIST_A_GLNSOLL_A
354
STW1 ZSW1
MIST_GL
WARN_CODE
FAULT_CODE
NIST_A_GL
IAIST_GL
NSOLL_A
<3>
<3>
<3>
<3>
Standard telegrams Manufacturer-specific telegrams Free telegram