Faults and Alarms
List of Faults and Alarms
3-724
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
F30662 Error in internal communications
Reaction: OFF2
Acknowledge: POWER ON
Cause: A module-internal communication error has occurred.
Fault value (r0949, interpret hexadecimal):
Only for internal Siemens troubleshooting.
Remedy: - carry out a POWER ON (power off/on).
- upgrade firmware to later version.
- contact the Hotline.
F30664 Error while booting
Reaction: OFF2
Acknowledge: POWER ON
Cause: An error has occurred during booting.
Fault value (r0949, interpret hexadecimal):
Only for internal Siemens troubleshooting.
Remedy: - carry out a POWER ON (power off/on).
- upgrade firmware to later version.
- contact the Hotline.
F30665 SI P2: System is defective
Reaction: OFF2
Acknowledge: IMMEDIATELY
Cause: A system defect was detected before the last boot or in the actual one. The system might have been rebooted (reset).
Fault value (r0949, interpret hexadecimal):
200000 hex, 400000 hex:
- Fault in the actual booting/operation.
Additional values:
- defect before the last time that the system booted.
Remedy: - carry out a POWER ON (power off/on).
- upgrade firmware to later version.
- contact the Hotline.
Re fault value = 400000 hex:
- ensure that the Control Unit is connected to the Power Module.
A30666 (F) SI Motion P2: Steady-state (static) 1 signal at the F-DI for safety-relevant
acknowledgement
Reaction: NONE
Acknowledge: NONE
Cause: A logical 1 signal is present at the F-DI configured in p10106 for more than 10 seconds.
If, at the F-DI no acknowledgment was performed for safe acknowledgment, then a steady-state logical and 0 signal
must be present. This avoids unintentional safety-relevant acknowledgement (or the "Internal Event Acknowledge"
signal) if a wire breaks or one of the two digital inputs bounces.
Remedy: Set the fail-safe digital input (F-DI) to a logical 0 signal (p10106).
Note:
F-DI: Failsafe Digital Input