Parameters
List of Parameters
1-324
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Description: Exits quick commissioning (p0010 = 1) with automatic calculation of all parameters of all existing drive data sets
that depend on the entries made during quick commissioning.
p3900 = 1 initially includes a parameter reset (factory setting, the same as p0970 = 1) for all parameters of the drive
object; however, without overwriting the entries made during the quick commissioning.
The interconnections of PROFIBUS PZD telegram selection (p0922) and the interconnections via p15 and p1500
are re-established and all of the dependent motor, open-loop and control-loop control parameters are calculated
(corresponding to p0340 = 1).
p3900 = 2 includes the restoration of the interconnections of PROFIBUS PZD telegram selection (p0922) and the
interconnections via p15 and p1500 and the calculations corresponding to p0340 = 1.
p3900 = 3 only includes the calculations associated with the motor, open-loop and closed-loop control parameters
corresponding to p0340 = 1.
Value: 0: No quick parameterization
1: Quick parameterization after parameter reset
2: Quick parameterization (only) for BICO and motor parameters
3: Quick parameterization for motor parameters (only)
Notice: After the value has been modified, no further parameter modifications can be made and the status is shown in
r3996. Modifications can be made again when r3996 = 0.
Note: When the calculations have been completed, p3900 and p0010 are automatically reset to a value of 0.
When calculating motor, open-loop and closed-loop control parameters (such as for p0340 = 1) parameters associ-
ated with a selected Siemens catalog motor are not overwritten.
If a catalog motor has not been selected (see p0300), then the following parameters are reset with p3900 > 0 in
order to restore the situation that applied when commissioning the drive for the first time:
for induction motors p0320, p0352, p0362 ... p0369, p0604, p0605, p0626 ... p0628.
for synchronous motors p0326, p0327, p0352, p0604, p0605.
Description: Displays the commissioning steps that have been carried out.
Note: The individual bits are only set if the appropriate action has been initiated and successfully completed.
When motor rating plate parameters are changed, the final display is reset.
When setting the individual bits, all of the most significant bits are reset.
p3900 Completion of quick commissioning / Compl quick_comm
Access level: 1 Calculated: - Data type: Integer16
Can be changed: C(1) Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0 3 0
r3925[0...n] Identification final display / Ident final_disp
Access level: 3 Calculated: p0340 = 1 Data type: Unsigned32
Can be changed: - Scaling: - Data set: DDS, p0180
Units group: - Unit selection: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Motor/control parameters calculated (p0340
= 1, p3900 > 0)
Yes No -
02 Motor data identification carried out at
standstill (p1910 = 1)
Yes No -
03 Rotating measurement carried out (p1960 =
1, 2)
Yes No -
15 Motor equivalent circuit diagram parameters
changed
Changed Not changed -