List of Parameters
Parameters
1-383
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Description: Displays the system utilization.
If the utilization is greater than 100%, fault F01054 is output.
Index: [0] = Reserved
[1] = Computing time utilization
[2] = Reserved
[3] = Reserved
[4] = Reserved
[5] = Largest total utilization
[6] = Reserved
[7] = Reserved
Dependency: Refer to: F01205
Note: Re index 1:
The value shows the total computing time load of the system.
Re index 5:
The total utilization is determined using all sampling times used. The largest total utilization is mapped here. The
sampling time with the largest total utilization is displayed in r9979.
Total utilization:
Computing time load of sampling time involved including load from higher-priority sampling times (interrupts).
Description: Diagnostics parameter to display additional information for internal software errors.
Note: Only for internal Siemens troubleshooting.
Description: Sets the monitoring time for the discrepancy for the digital inputs.
The signal states at the two associated digital inputs (F-DI) must assume the same state within this monitoring time.
Dependency: Refer to: p10102
Note: F-DI: Failsafe Digital Input
r9976[0...7] System utilization / Sys util
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- [%] - [%] - [%]
r9999[0...99] Software error internal supplementary diagnostics / SW_err int diag
Access level: 4 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - -
p10002 SI discrepancy monitoring time (processor 1) / SI discrp t_mon P1
CU240E-2 DP F
CU240E-2 F
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: C(95) Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
1.00 [ms] 2000.00 [ms] 500.00 [ms]