List of Parameters
Parameters
1-339
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Description: Sets the shutdown speed for the pulse suppression.
Below this speed "standstill" is assumed and for STOP B / SS1, the pulses are suppressed (by changing to STOP
A).
Dependency: Refer to: p9356, p9560
Notice: This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note: SS1: Safe Stop 1
Description: Sets the stop response for the function "Safely-Limited Speed" (SLS).
These settings apply to the individual limit values for SLS.
Value: 0: STOP A
1: STOP B
Index: [0] = Limit value SLS1
[1] = Limit value SLS2
[2] = Limit value SLS3
[3] = Limit value SLP4
Dependency: Refer to: p9331, p9563
Notice: This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note: SLS: Safely-Limited Speed
Description: Sets the tolerance for the function "Safe motion direction" (SDI). This motion in the monitored direction is still per-
missible before an alarm is initiated.
Dependency: Refer to: p9365, p9366
Refer to: C30716
Notice: This parameter is overwritten by the copy function of the safety functions integrated in the drive. Sets the tolerance
for the function "Safe motion direction" (SDI).
Note: SDI: Safe Direction (safe motion direction)
p9360 SI Motion pulse suppression shutdown speed (processor 2) / SI Mtn IL n_sh P2
CU240E-2 DP F
CU240E-2 F
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: C(95) Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
10.00 [rpm] 6000.00 [rpm] 10.00 [rpm]
p9363[0...3] SI Motion SLS stop response (processor 2) / SI Mtn SLS stop P2
CU240E-2 DP F
CU240E-2 F
Access level: 3 Calculated: - Data type: Integer16
Can be changed: C(95) Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0 1 0
p9364 SI Motion SDI tolerance (processor 2) / SI Mtn SDI tol P2
CU240E-2 DP F
CU240E-2 F
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: C(95) Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0.001 [°] 360.000 [°] 12.000 [°]