Siemens SINAMICS G120 - p2184[0...n] Load monitoring speed threshold value 3; n_thresh 3; p2185[0...n] Load monitoring torque threshold 1, upper; M_thresh 1 upper; p2186[0...n] Load monitoring torque threshold 1, lower; M_thresh 1 lower; p2187[0...n] Load monitoring torque threshold 2, upper; M_thresh 2 upper

Siemens SINAMICS G120
750 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of Parameters
Parameters
1-293
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Description: Sets the speed/torque envelope curve for load monitoring.
The envelope curve (upper and lower envelope curve) is defined as follows based on 3 speed thresholds:
p2182 (n_threshold 1) --> p2185 (M_threshold 1, upper), p2186 (M_threshold 1, lower)
p2183 (n_threshold 2) --> p2187 (M_threshold 2, upper), p2188 (M_threshold 2, lower)
p2184 (n_threshold 3) --> p2189 (M_threshold 3, upper), p2190 (M_threshold 3, lower)
Dependency: The following applies: p2182 < p2183 < p2184
Refer to: p2182, p2183, p2189, p2190
Description: Sets the speed/torque envelope curve for load monitoring.
Dependency: The following applies: p2185 > p2186
Refer to: p2182, p2186
Note: The upper envelope curve is defined by p2185, p2187 and p2189.
Description: Sets the speed/torque envelope curve for load monitoring.
Dependency: The following applies: p2186 < p2185
Refer to: p2182, p2185
Note: The lower envelope curve is defined by p2186, p2188 and p2190.
Description: Sets the speed/torque envelope curve for load monitoring.
Dependency: The following applies: p2187 > p2188
Refer to: p2183, p2188
Note: The upper envelope curve is defined by p2185, p2187 and p2189.
p2184[0...n] Load monitoring speed threshold value 3 / n_thresh 3
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: 3_1 Unit selection: p0505
Min Max Factory setting
0.00 [rpm] 210000.00 [rpm] 1500.00 [rpm]
p2185[0...n] Load monitoring torque threshold 1, upper / M_thresh 1 upper
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: 7_1 Unit selection: p0505
Min Max Factory setting
0.00 [Nm] 20000000.00 [Nm] 10000000.00 [Nm]
p2186[0...n] Load monitoring torque threshold 1, lower / M_thresh 1 lower
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: 7_1 Unit selection: p0505
Min Max Factory setting
0.00 [Nm] 20000000.00 [Nm] 0.00 [Nm]
p2187[0...n] Load monitoring torque threshold 2, upper / M_thresh 2 upper
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: 7_1 Unit selection: p0505
Min Max Factory setting
0.00 [Nm] 20000000.00 [Nm] 10000000.00 [Nm]