EasyManua.ls Logo

Siemens SINAMICS G120 - p1500[0...n] Torque setpoint selection; M_set sel

Siemens SINAMICS G120
750 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of Parameters
Parameters
1-207
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Description: Sets the source for the torque setpoint.
For single-digit values, the following applies:
The value specifies the main setpoint.
For double-digit values, the following applies:
The left-hand digit specifies the supplementary setpoint, the right-hand digit the main setpoint.
Example:
Value = 26
--> The analog setpoint (2) supplies the supplementary setpoint.
--> The fieldbus (6) supplies the main setpoint.
Value: 0: No main setpoint
2: Analog setpoint
6: Fieldbus
20: Analog setpoint + no main setpoint
22: Analog setpoint + analog setpoint
26: Analog setpoint + fieldbus
60: Fieldbus + no main setpoint
62: Fieldbus + analog setpoint
66: Fieldbus+fieldbus
Dependency: When changing this parameter, the following settings are influenced:
Refer to: p1503, p1511
Caution: When executing a specific macro, the corresponding programmed settings are made and become active.
p1500[0...n] Torque setpoint selection / M_set sel
CU240B-2 DP Access level: 2 Calculated: - Data type: Integer16
Can be changed: C(1), T Scaling: - Data set: CDS, p0170
Units group: - Unit selection: -
Min Max Factory setting
0 66 6