EasyManua.ls Logo

Siemens SINAMICS G120 - A07910 (N) Drive: Motor overtemperature; A07920 Drive: Torque;speed too low; A07921 Drive: Torque;speed too high; A07922 Drive: Torque;speed out of tolerance

Siemens SINAMICS G120
750 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of Faults and Alarms
Faults and Alarms
3-701
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
A07910 (N) Drive: Motor overtemperature
Reaction: NONE
Acknowledge: NONE
Cause: KTY or no sensor:
The measured motor temperature or the temperature of the thermal model has exceeded the alarm threshold
(p0604). The response parameterized in p0610 becomes active.
PTC or bimetallic NC contact:
The response threshold of 1650 Ohm was exceeded or the NC contact opened.
Alarm value (r2124, interpret decimal):
11: No output current reduction.
12: Output current reduction active.
See also: p0604 (Motor temperature alarm threshold), p0610 (Motor overtemperature response)
Remedy: - check the motor load.
- check the motor ambient temperature.
- check KTY84.
- check temperatures of the thermal model (p0626 ... p0628).
A07920 Drive: Torque/speed too low
Reaction: NONE
Acknowledge: NONE
Cause: For p2193 = 1:
The torque deviates from the torque/speed envelope characteristic (too low).
For p2193 = 2:
The speed signal from the external encoder (refer to p3230) deviates from the speed (r2169) (too low).
See also: p2181 (Load monitoring response)
Remedy: - check the connection between the motor and load.
- adapt the parameterization corresponding to the load.
A07921 Drive: Torque/speed too high
Reaction: NONE
Acknowledge: NONE
Cause: For p2193 = 1:
The torque deviates from the torque/speed envelope characteristic (too high).
For p2193 = 2:
The speed signal from the external encoder (refer to p3230) deviates from the speed (r2169) (too high).
Remedy: - check the connection between the motor and load.
- adapt the parameterization corresponding to the load.
A07922 Drive: Torque/speed out of tolerance
Reaction: NONE
Acknowledge: NONE
Cause: For p2193 = 1:
The torque deviates from the torque/speed envelope characteristic.
For p2193 = 2:
The speed signal from the external encoder (refer to p3230) deviates from the speed (r2169).
Remedy: - check the connection between the motor and load.
- adapt the parameterization corresponding to the load.
F07923 Drive: Torque/speed too low
Reaction: OFF1 (NONE, OFF2, OFF3)
Acknowledge: IMMEDIATELY
Cause: For p2193 = 1:
The torque deviates from the torque/speed envelope characteristic (too low).
For p2193 = 2:
The speed signal from the external encoder (refer to p3230) deviates from the speed (r2169) (too low).
Remedy: - check the connection between the motor and load.
- adapt the parameterization corresponding to the load.