Siemens SINAMICS G120 - p2215[0...n] CO: Technology controller, fixed value 15; Tec_ctr fix val 15; p2216[0...n] Technology controller fixed value selection method; Tec_ctr FixVal sel; p2220[0...n] BI: Technology controller fixed value selection bit 0; Tec_ctrl sel bit 0; p2221[0...n] BI: Technology controller fixed value selection bit 1; Tec_ctrl sel bit 1

Siemens SINAMICS G120
750 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of Parameters
Parameters
1-301
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Description: Sets the value for fixed value 15 of the technology controller.
Dependency: Refer to: p2220, p2221, p2222, p2223, r2224, r2229
Notice: A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Description: Selects the method that can be used to select the fixed setpoints.
Value: 1: Fixed value selection direct
2: Fixed value selection binary
Description: Sets the signal source to select the fixed value of the technology controller.
Dependency: Refer to: p2221, p2222, p2223
Description: Sets the signal source to select the fixed value of the technology controller.
Dependency: Refer to: p2220, p2222, p2223
Description: Sets the signal source to select the fixed value of the technology controller.
Dependency: Refer to: p2220, p2221, p2223
p2215[0...n] CO: Technology controller, fixed value 15 / Tec_ctr fix val 15
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Data set: DDS, p0180
Units group: 9_1 Unit selection: p0595
Min Max Factory setting
-200.00 [%] 200.00 [%] 150.00 [%]
p2216[0...n] Technology controller fixed value selection method / Tec_ctr FixVal sel
Access level: 2 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Data set: DDS, p0180
Units group: - Unit selection: -
Min Max Factory setting
1 2 1
p2220[0...n] BI: Technology controller fixed value selection bit 0 / Tec_ctrl sel bit 0
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Data set: CDS, p0170
Units group: - Unit selection: -
Min Max Factory setting
- - 0
p2221[0...n] BI: Technology controller fixed value selection bit 1 / Tec_ctrl sel bit 1
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Data set: CDS, p0170
Units group: - Unit selection: -
Min Max Factory setting
- - 0
p2222[0...n] BI: Technology controller fixed value selection bit 2 / Tec_ctrl sel bit 2
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Data set: CDS, p0170
Units group: - Unit selection: -
Min Max Factory setting
- - 0