Siemens SINAMICS G120 - p3326[0...n] Fluid flow machine P = f(n), Y coordinate: P flow4 %, point 4; Fluid flow mach Y4; p3327[0...n] Fluid flow machine P = f(n), X coordinate: n flow4 %, point 4; Fluid flow mach X4; p3328[0...n] Fluid flow machine P = f(n), Y coordinate: P flow5 %, point 5; Fluid flow mach Y5; p3329[0...n] Fluid flow machine P = f(n), X coordinate: n flow5 %, point 5; Fluid flow mach X5

Siemens SINAMICS G120
750 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of Parameters
Parameters
1-321
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Description: The power (P) for point 4 on the Y coordinate of the flow characteristic is saved in p3326. Unit: %
Dependency: Refer to: p3327
Note: The reference value for power and speed is the rated power/rated speed.
The energy saved is displayed in r0041.
Description: The speed (n) for point 4 on the X coordinate of the flow characteristic is saved in p3327. Unit: %
Dependency: Refer to: p3326
Note: The reference value for power and speed is the rated power/rated speed.
The energy saved is displayed in r0041.
Description: The power (P) for point 5 on the Y coordinate of the flow characteristic is saved in p3328. Unit: %
Dependency: Refer to: p3329
Note: The reference value for power and speed is the rated power/rated speed.
The energy saved is displayed in r0041.
Description: The speed (n) for point 5 on the X coordinate of the flow characteristic is saved in p3329. Unit: %
Dependency: Refer to: p3328
Note: The reference value for power and speed is the rated power/rated speed.
The energy saved is displayed in r0041.
p3326[0...n] Fluid flow machine P = f(n), Y coordinate: P flow4 %, point 4 / Fluid flow mach Y4
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: - Unit selection: -
Min Max Factory setting
0.00 100.00 92.00
p3327[0...n] Fluid flow machine P = f(n), X coordinate: n flow4 %, point 4 / Fluid flow mach X4
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: - Unit selection: -
Min Max Factory setting
0.00 100.00 75.00
p3328[0...n] Fluid flow machine P = f(n), Y coordinate: P flow5 %, point 5 / Fluid flow mach Y5
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: - Unit selection: -
Min Max Factory setting
0.00 100.00 100.00
p3329[0...n] Fluid flow machine P = f(n), X coordinate: n flow5 %, point 5 / Fluid flow mach X5
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: - Unit selection: -
Min Max Factory setting
0.00 100.00 100.00