EasyManua.ls Logo

Siemens SINAMICS G120 - Fig. 2-35 2451 - ZSW1 status word interconnection (p2038 = 2)

Siemens SINAMICS G120
750 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Communication
Function diagrams
2-533
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Fig. 2-35 2451 – ZSW1 status word interconnection (p2038 = 2)
- 2451 -
Function diagram
87654321
FP_2451_97_61.vsd
PROFIdrive / PROFIBUS
G120 CU240B/E-2 DP
13.12.2010 V4.4
ZSW1 status word interconnection (p2038 = 2)
<1>
<2>
<3>
ZSW1.0
ZSW1.1
ZSW1.2
ZSW1.3
ZSW1.4
ZSW1.5
ZSW1.6
ZSW1.8
ZSW1.9
ZSW1.11
ZSW1.12
ZSW1.13
ZSW1.14
ZSW1.15
ZSW1.7
ZSW1.10
<3>
p2080[2] = r0899.2
p2080[3] = r2139.3
p2080[4] = r0899.4
p2080[5] = r0899.5
p2080[6] = r0899.6
p2080[7] = r2139.7
p2080[8] = r2197.7
p2080[9] = r0899.9
p2080[10] = r2199.1
p2080[11] = r0056.13
-
p2080[13] = r2135.14
p2080[0] = r0899.0
p2080[1] = r0899.1
p2080[14] = r2197.3
[2503.7]
[2548.7]
[2503.7]
[2503.7]
[2503.7]
[2548.7]
[2534.7]
[2503.7]
[2536.7]
[2522.7]
-
[2548.7]
-
[2503.7]
[2503.7]
[2534.7]
[8060]
[8065]
[8011]
[2503]
[8010]
[6060]
-
[8016]
-
[8011]
<1>
-
-
-
-
-
-
-
-
-
-
-
-
-
-
<2>
p2080[15] = r0836.0
<4>
Signal sources for ZSW1 in Interface Mode VIK-NAMUR (p2038 = 2)
Signal
Meaning
Interconnection
parameters
[Function diagram]
internal control word
[Function diagram]
signal target
Inverted
1 = Ready for switching on
1 = Ready for operation (DC link loaded, pulses inhibited)
1 = Operation enabled (drive follows n_set)
1 = Fault present
1 = No coast down active (OFF2 inactive)
1 = No fast stop active (OFF3 inactive)
1 = Switching on inhibited active
1 = Alarm present
1 = Speed setpoint - actual value deviation within tolerance t_off
1 = Control requested
1 = f or n comparison value reached/exceeded
1 = I, M, or P limit not reached
1 = No motor overtemperature alarm
1 = Motor rotates forwards (n_act  0)
0 = Motor rotates backwards (n_act < 0)
1 = Display CDS
Reserved
Used in telegram 20.
The ZSW1 is generated using the binector-connector converter (BI: p2080[0...15], inversion: p2088[0].0...p2088[0].15)
The drive object is ready to accept data.
Sequence control
Sequence control
Sequence control
Sequence control
Sequence control
Sequence control
<4>
Interconnection is not disabled.

Table of Contents

Other manuals for Siemens SINAMICS G120

Related product manuals