Siemens SINAMICS G120 - p1654[0...n] Curr. setpoint torque-gen. smoothing time field weakening range; Isq_s T_smth FW; p1702[0...n] Isd current controller pre-control scaling; Isd_ctr_prectrScal; p1703[0...n] Isq current controller pre-control scaling; Isq_ctr_prectrScal; p1715[0...n] Current controller P gain; I_ctrl Kp

Siemens SINAMICS G120
750 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters
List of Parameters
1-222
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Description: Sets the smoothing time constant for the setpoint of the torque-generating current components.
Note: The smoothing time does not become effective until the field-weakening range is reached.
Description: Sets the scaling of the dynamic current controller pre-control for the flux-generating current component Isd.
Note: The parameter is effective for permanent-magnet synchronous motors.
Description: Sets the scaling of the dynamic current controller pre-control for the torque/force-generating current component Isq.
Description: Sets the proportional gain of the current controller.
This value is automatically pre-set using p3900 or p0340 when commissioning has been completed.
Description: Sets the integral-action time of the current controller.
Dependency: Refer to: p1715
p1654[0...n] Curr. setpoint torque-gen. smoothing time field weakening range / Isq_s T_smth FW
Access level: 4 Calculated: p0340 = 1 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: - Unit selection: -
Min Max Factory setting
0.1 [ms] 50.0 [ms] 4.8 [ms]
p1702[0...n] Isd current controller pre-control scaling / Isd_ctr_prectrScal
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: - Unit selection: -
Min Max Factory setting
0.0 [%] 200.0 [%] 70.0 [%]
p1703[0...n] Isq current controller pre-control scaling / Isq_ctr_prectrScal
Access level: 4 Calculated: p0340 = 1,3,4 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: - Unit selection: -
Min Max Factory setting
0.0 [%] 200.0 [%] 60.0 [%]
p1715[0...n] Current controller P gain / I_ctrl Kp
Access level: 4 Calculated: p0340 = 1,3,4 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: - Unit selection: -
Min Max Factory setting
0.000 100000.000 0.000
p1717[0...n] Current controller integral-action time / I_ctrl Tn
Access level: 4 Calculated: p0340 = 1,3,4 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: - Unit selection: -
Min Max Factory setting
0.00 [ms] 1000.00 [ms] 2.00 [ms]