EasyManua.ls Logo

Siemens SINAMICS G120 - p0819[0...2] Copy Drive Data Set DDS; Copy DDS; p0820[0...n] BI: Drive Data Set selection DDS bit 0; DDS select., bit 0; p0821[0...n] BI: Drive Data Set selection DDS bit 1; DDS select., bit 1

Siemens SINAMICS G120
750 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of Parameters
Parameters
1-111
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Description: Copies one Drive Data Set (DDS) into another.
Index: [0] = Source Drive Data Set
[1] = Target Drive Data Set
[2] = Start copying procedure
Dependency: Refer to: r3996
Notice: When the drive data sets are copied, short-term communication interruptions may occur.
Note: Procedure:
1. In Index 0, enter which drive data set is to be copied.
2. In Index 1, enter the drive data set data that is to be copied into.
3. Start copying: Set index 2 from 0 to 1.
p0819[2] is automatically set to 0 when copying is completed.
Description: Sets the signal source to select the Drive Data Set, bit 0 (DDS, bit 0).
Dependency: Refer to: r0051, p0826, r0837
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description: Sets the signal source to select the Drive Data Set, bit 1 (DDS, bit 1).
Dependency: Refer to: r0051, r0837
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p0819[0...2] Copy Drive Data Set DDS / Copy DDS
Access level: 2 Calculated: - Data type: Unsigned8
Can be changed: C(15) Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0 3 0
p0820[0...n] BI: Drive Data Set selection DDS bit 0 / DDS select., bit 0
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: C(15), T Scaling: - Data set: CDS, p0170
Units group: - Unit selection: -
Min Max Factory setting
- - 0
p0821[0...n] BI: Drive Data Set selection DDS bit 1 / DDS select., bit 1
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: C(15), T Scaling: - Data set: CDS, p0170
Units group: - Unit selection: -
Min Max Factory setting
- - 0