Siemens SINAMICS G120 - p0628[0...n] Motor overtemperature rotor winding; Mot T_over rotor; r0630[0...n] Motor temperature model ambient temperature; MotTMod T_amb.; r0631[0...n] Motor temperature model, stator core temperature; MotTMod T_core; r0632[0...n] Motor temperature model, stator winding temperature; MotTMod T_copper

Siemens SINAMICS G120
750 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of Parameters
Parameters
1-85
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Description: Defines the rated overtemperature of the squirrel cage rotor referred to ambient temperature.
Dependency: For 1LA7 motors (refer to p0300), the parameter is pre-set as a function of p0307 and p0311.
Refer to: p0625
Note: When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (refer to p0300).
Description: Displays the ambient temperature of the motor temperature model.
Description: Displays the stator core temperature of the motor temperature model.
Description: Displays the stator winding temperature of the motor temperature model.
Description: Displays the rotor temperature of the motor temperature model.
p0628[0...n] Motor overtemperature rotor winding / Mot T_over rotor
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: C(3), U, T Scaling: - Data set: MDS
Units group: 21_2 Unit selection: p0505
Min Max Factory setting
20 [K] 200 [K] 100 [K]
r0630[0...n] Motor temperature model ambient temperature / MotTMod T_amb.
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2006 Data set: MDS
Units group: 21_1 Unit selection: p0505
Min Max Factory setting
- [°C] - [°C] - [°C]
r0631[0...n] Motor temperature model, stator core temperature / MotTMod T_core
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2006 Data set: MDS
Units group: 21_1 Unit selection: p0505
Min Max Factory setting
- [°C] - [°C] - [°C]
r0632[0...n] Motor temperature model, stator winding temperature / MotTMod T_copper
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2006 Data set: MDS
Units group: 21_1 Unit selection: p0505
Min Max Factory setting
- [°C] - [°C] - [°C]
r0633[0...n] Motor temperature model, rotor temperature / MotTMod T_rotor
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2006 Data set: MDS
Units group: 21_1 Unit selection: p0505
Min Max Factory setting
- [°C] - [°C] - [°C]