List of Parameters
Parameters
1-365
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Description: Status signal for safety-relevant motion monitoring functions integrated in the drive.
Notice: Re bit 07:
An internal event is displayed if a STOP A ... F is active.
The signal state behaves in an opposite way to the PROFIsafe Standard.
Note: This parameter is only supplied with actual values if SI Motion functions are active. For Safety Integrated Basic
Functions (STO), the value is equal to zero.
Description: Status signal for safety-relevant motion monitoring functions integrated in the drive.
Notice: Re bit 07:
An internal event is displayed if a STOP A ... F is active.
The signal state behaves in an opposite way to the PROFIsafe Standard.
Note: This parameter is only supplied with actual values if SI Motion functions are active. For Safety Integrated Basic
Functions (STO), the value is equal to zero.
r9722.0...15 CO/BO: SI Motion status signals integrated in the drive / SI Mtn integ stat
CU240E-2 DP F Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 STO active Yes No -
01 SS1 active Yes No -
04 SLS active Yes No -
07 Internal event No Yes -
09 Active SLS stage bit 0 Set Not set -
10 Active SLS stage bit 1 Set Not set -
12 SDI pos active Yes No 2861
13 SDI neg active Yes No 2861
15 SSM (speed below limit value) Yes No 2860
r9722.0...13 CO/BO: SI Motion status signals integrated in the drive / SI Mtn integ stat
CU240E-2 F Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 STO active Yes No -
01 SS1 active Yes No -
04 SLS active Yes No -
07 Internal event No Yes -
09 Active SLS stage bit 0 Set Not set -
10 Active SLS stage bit 1 Set Not set -
12 SDI pos active Yes No 2861
13 SDI neg active Yes No 2861