EasyManua.ls Logo

Siemens SINAMICS G120 - r0070 CO: Actual DC link voltage; Vdc act val; r0071 Maximum output voltage; U_output max; r0072 CO: Output voltage; U_output; r0073 Maximum modulation depth; Modulat_depth max

Siemens SINAMICS G120
750 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters
List of Parameters
1-38
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Description: Displays the measured actual value of the DC link voltage.
Dependency: Refer to: r0026
Notice: When measuring a DC link voltage < 200 V, for the Power Module (e.g. PM240) a valid measured value is not sup-
plied. In this case, when an external 24 V power supply is connected, a value of approx. 24 V is displayed in the dis-
play parameter.
Note: The DC link voltage is available smoothed (r0026) and unsmoothed (r0070).
Description: Displays the maximum output voltage.
Dependency: The maximum output voltage depends on the actual DC link voltage (r0070) and the maximum modulation depth
(p1803).
Note: As the (driven) motor load increases, the maximum output voltage drops as a result of the reduction in DC link volt-
age.
Description: Displays the actual output voltage of the power unit.
Dependency: Refer to: r0025
Note: The output voltage is available smoothed (r0025) and unsmoothed (r0072).
Description: Displays the maximum modulation depth.
Dependency: Refer to: p1803
r0070 CO: Actual DC link voltage / Vdc act val
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2001 Data set: -
Units group: 5_2 Unit selection: p0505
Min Max Factory setting
- [V] - [V] - [V]
r0071 Maximum output voltage / U_output max
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2001 Data set: -
Units group: 5_1 Unit selection: p0505
Min Max Factory setting
- [Vrms] - [Vrms] - [Vrms]
r0072 CO: Output voltage / U_output
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2001 Data set: -
Units group: 5_1 Unit selection: p0505
Min Max Factory setting
- [Vrms] - [Vrms] - [Vrms]
r0073 Maximum modulation depth / Modulat_depth max
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- [%] - [%] - [%]