Parameters
List of Parameters
1-386
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Description: Sets the fail-safe digital input (F-DI) for the "SLS" function.
Value: 0: Statically active
1: F-DI 0
2: F-DI 1
3: F-DI 2
255: Statically inact
Dependency: Refer to: p10126
Note: If value = 0:
No terminal assigned, safety function always active.
If value = 255:
No terminal assigned, safety function always inactive.
F-DI: Failsafe Digital Input
SLS: Safely-Limited Speed
Description: Sets the fail-safe digital input (F-DI) for the "SDI positive" function.
Value: 0: Statically active
1: F-DI 0
2: F-DI 1
3: F-DI 2
255: Statically inact
Note: If value = 0:
No terminal assigned, safety function always active.
If value = 255:
No terminal assigned, safety function always inactive.
F-DI: Failsafe Digital Input
SDI: Safe Direction (safe motion direction)
Description: Sets the fail-safe digital input (F-DI) for the "SDI negative" function.
Value: 0: Statically active
1: F-DI 0
2: F-DI 1
3: F-DI 2
255: Statically inact
Note: If value = 0:
No terminal assigned, safety function always active.
If value = 255:
No terminal assigned, safety function always inactive.
F-DI: Failsafe Digital Input
SDI: Safe Direction (safe motion direction)
p10026 SI SLS input terminal (processor 1) / SI SLS F-DI P1
CU240E-2 DP F
CU240E-2 F
Access level: 3 Calculated: - Data type: Integer16
Can be changed: C(95) Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0 255 0
p10030 SI SDI positive input terminal (processor 1) / SI SDI pos F-DI P1
CU240E-2 DP F
CU240E-2 F
Access level: 3 Calculated: - Data type: Integer16
Can be changed: C(95) Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0 255 0
p10031 SI SDI negative input terminal (processor 1) / SI SDI neg F-DI P1
CU240E-2 DP F
CU240E-2 F
Access level: 3 Calculated: - Data type: Integer16
Can be changed: C(95) Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0 255 0