Siemens SINAMICS G120 - p1121[0...n] Ramp-function generator ramp-down time; RFG ramp­down time; p1122[0...n] BI: Bypass ramp-function generator; Bypass RFG; p1123[0...n] Ramp-function generator minimum ramp-up time; RFG t_RU min; p1127[0...n] Ramp-function generator minimum ramp-down time; RFG t_RD min

Siemens SINAMICS G120
750 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters
List of Parameters
1-154
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Description: The ramp-function generator ramps-down the speed setpoint from the maximum speed (p1082) down to standstill
(setpoint = 0) in this time.
Further, the ramp-down time is always effective for OFF1.
Dependency: Refer to: p1082, p1123
Note: For U/f control and sensorless vector control (see p1300), ramp-down times of 0 s are not recommended. The set-
ting should be based on the startup times (r0345) of the motor.
Description: Sets the signal source for bypassing the ramp generator (ramp-up and ramp-down times = 0).
Caution: If the technology controller is operated in mode p2251 = 0 (technology controller as main speed setpoint), then it is
not permissible to disable the interconnection to its status word (r2349).
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: In the case of sensorless vector control, the ramp-function generator must not be bypassed, other than indirectly by
means of interconnection with r2349.
Description: Sets the minimum ramp-up time.
The ramp-up time (p1120) is limited internally to this minimum value.
Dependency: Refer to: p1082
Note: For U/f control and sensorless vector control (see p1300), ramp-down times of 0 s are not recommended. The set-
ting should be based on the startup times (r0345) of the motor.
If the maximum speed p1082 changes, p1123 is re-calculated.
Description: Sets the minimum ramp-down time.
The ramp-down time (p1121) is limited internally to this minimum value.
Dependency: Refer to: p1082
Note: For U/f control and sensorless vector control (see p1300), ramp-down times of 0 s are not recommended. The set-
ting should be based on the startup times (r0345) of the motor. If the maximum speed p1082 changes, p1123 is re-
calculated.
p1121[0...n] Ramp-function generator ramp-down time / RFG ramp-down time
PM240
PM250, PM260
Access level: 1 Calculated: - Data type: FloatingPoint32
Can be changed: C(1), U, T Scaling: - Data set: DDS, p0180
Units group: - Unit selection: -
Min Max Factory setting
0.000 [s] 999999.000 [s] 10.000 [s]
p1122[0...n] BI: Bypass ramp-function generator / Bypass RFG
Access level: 4 Calculated: - Data type: U32 / Binary
Can be changed: U, T Scaling: - Data set: CDS, p0170
Units group: - Unit selection: -
Min Max Factory setting
- - 0
p1123[0...n] Ramp-function generator minimum ramp-up time / RFG t_RU min
Access level: 4 Calculated: p0340 = 1 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: - Unit selection: -
Min Max Factory setting
0.000 [s] 999999.000 [s] 0.000 [s]
p1127[0...n] Ramp-function generator minimum ramp-down time / RFG t_RD min
Access level: 4 Calculated: p0340 = 1 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: - Unit selection: -
Min Max Factory setting
0.000 [s] 999999.000 [s] 0.000 [s]