Parameters
List of Parameters
1-160
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Description: Sets the signal source for the command "enable setpoint/inhibit setpoint".
For the PROFIdrive profile, this command corresponds to control word 1 bit 6 (STW1.6).
BI: p1142 = 0 signal
Inhibits the setpoint (the ramp-function generator input is set to zero).
BI: p1142 = 1 signal
Enables the setpoint.
Dependency: Refer to: p1140, p1141
Caution: When "master control from PC" is activated, this binector input is ineffective.
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description: Sets the signal source for accepting the setting value of the ramp-function generator.
Dependency: The signal source for the ramp-function generator setting value is set using parameters.
Refer to: p1144
Note: 0/1 signal:
The ramp-function generator output is immediately (without delay) set to the setting value of the ramp-function gen-
erator.
1 signal:
The setting value of the ramp-function generator is effective.
1/0 signal:
The input value of the ramp-function generator is effective. The ramp-function generator output is adapted to the
input value using the ramp-up time or the ramp-down time.
0 signal:
The input value of the ramp-function generator is effective.
Description: Sets the signal source for the ramp-function generator setting value.
Dependency: The signal source for accepting the setting value is set using parameters.
Refer to: p1143
p1142[0...n] BI: Enable setpoint/inhibit setpoint / Setpoint enable
CU240B-2 DP
CU240E-2 DP
CU240E-2 DP F
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Data set: CDS, p0170
Units group: - Unit selection: -
Min Max Factory setting
- - [0] 2090.6
[1] 1
[2] 2090.6
[3] 2090.6
p1143[0...n] BI: Ramp-function generator, accept setting value / RFG accept set v
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Data set: CDS, p0170
Units group: - Unit selection: -
Min Max Factory setting
- - 0
p1144[0...n] CI: Ramp-function generator setting value / RFG setting value
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: U, T Scaling: p2000 Data set: CDS, p0170
Units group: - Unit selection: -
Min Max Factory setting
- - 0