Siemens SINAMICS G120 - p1145[0...n] Ramp-function generator tracking intensity.; RFG track intens; p1148[0...n] Ramp-function gen., tolerance for ramp-up and ramp-down active; RFG tol HL;RL act; r1149 CO: Ramp-function generator, acceleration; RFG acceleration; r1150 CO: Ramp-function generator speed setpoint at the output; RFG n_set at outp

Siemens SINAMICS G120
750 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of Parameters
Parameters
1-161
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Description: Sets the ramp-function generator tracking.
The output value of the ramp-function generator is tracked (corrected) corresponding to the maximum possible
drive acceleration. The reference value is the deviation at the speed/velocity controller input that is necessary to
ensure that the motor accelerates at the torque/force limit.
Notice: If ramp-function generator tracking is activated and the ramp time is set too short, this can cause unsteady acceler-
ation.
Remedy:
- switch off ramp-function generator tracking (p1145 = 0).
- increase the ramp-up/ramp-down time (p1120, p1121).
Note: In the U/f mode, ramp-function generator tracking is not active.
Description: Sets the tolerance value for the status of the ramp-function generator (ramp-up active, ramp-down active).
If the input of the ramp-function generator does not change in comparison to the output by more than the entered
tolerance time, then the status bits "ramp-up active" and "ramp-down active" are not influenced.
Dependency: Refer to: r1199
Description: Displays the acceleration of the ramp-function generator.
Dependency: Refer to: p1145
Description: Displays the setpoint at the output of the ramp-function generator.
p1145[0...n] Ramp-function generator tracking intensity. / RFG track intens
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: - Unit selection: -
Min Max Factory setting
0.0 50.0 0.0
p1148[0...n] Ramp-function gen., tolerance for ramp-up and ramp-down active / RFG tol HL/RL act
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: 3_1 Unit selection: p0505
Min Max Factory setting
0.000 [rpm] 1000.000 [rpm] 19.800 [rpm]
r1149 CO: Ramp-function generator, acceleration / RFG acceleration
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2007 Data set: -
Units group: 39_1 Unit selection: p0505
Min Max Factory setting
- [rev/s²] - [rev/s²] - [rev/s²]
r1150 CO: Ramp-function generator speed setpoint at the output / RFG n_set at outp
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2000 Data set: -
Units group: 3_1 Unit selection: p0505
Min Max Factory setting
- [rpm] - [rpm] - [rpm]