EasyManua.ls Logo

Siemens SINAMICS G120 - A50517 FBLOCKS: Int. meas. active; F50518 FBLOCKS: Sampling time of free run-time group differs at download

Siemens SINAMICS G120
750 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Faults and Alarms
List of Faults and Alarms
3-732
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
A50517 FBLOCKS: Int. meas. active
Reaction: NONE
Acknowledge: NONE
Cause: A Siemens internal measurement has been activated.
Remedy: Carry out a POWER ON (power off/on) for the Control Unit involved.
F50518 FBLOCKS: Sampling time of free run-time group differs at download
Reaction: NONE
Acknowledge: IMMEDIATELY
Cause: In the STARTER/SCOUT project that was downloaded, the hardware sampling time of a free run-time group (1 <=
p20000[i] <= 256) was set to a value that was either too low or too high.
The sampling time must be between 1 ms and the value r20003 - r20002.
If the sampling time of the selected free run-time group is < 1 ms, the equivalent value of 1 ms is used.
If the value >= r20003, then the sampling time is set to the next higher or the same software sampling time >= r21003.
Fault value (r0949, decimal interpretation):
Number of the p20000 index of the run-time group where the sampling time is incorrectly set.
Number of the run-time group = fault value + 1
Note:
For SIMOTION D410, r20003 (unlike all the other Control Units) is automatically set the same as the PROFIBUS
sampling time.
Remedy: - correctly set the sampling time of the run-time group.
- if required, take all of the blocks from the run-time group.
Note:
Fault F50518 only detects an incorrectly parameterized run-time group. If, after correcting p20000[i] in the project,
this error occurs again at download, then the run-time group involved should be identified using the fault value
(r0949) and the sampling time correctly set.