Function diagrams
Safety Integrated
2-566
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Fig. 2-65 2825 – SI Motion, SS1: Safe Stop 1, Internal STOP A, B, F
- 2825 -
Function diagram
87654321
FP_2825_97_53.vsd
Safety Integrated
G120 CU240E-2 F/DP F
13.12.2010 V4.4
SI Motion, SS1: Safe Stop 1, Internal STOP A, B, F
T0
STOP F --> STOP A
[2840.4]
[2830.2]
[2840.4]
SI Mtn integ STW
r9720
r9720
.1
SI Mtn integ STW
r9720
r9720
.0
Safe brake-ramp monitoring
STO initiate
[2840.8]
SI Mtn integ stat
r9722
r9722
.0
[2840.4]
SI Mtn integ stat
r9722
r9722
.1
SS1: Safe Stop 1
SS1 active
STO deselection
SS1 deselection
STO active
SI Mtn rp t_del P2
10000.00 ... 99000000.00 [μs]
p9382 (250000.00)
SI Mtn ramp t P1
10.00 ... 99000.00 [ms]
p9582 (250.00)
SI Mtn ramp ref P1
600.0000 ... 24000.0000 [1/min]
p9581 (1500.0000)
SI Mtn rp t_mon P1
0.50 ... 1000.00 [s]
p9583 (10.00)
SI Mtn ramp ref P2
600.0000 ... 24000.0000 [1/min]
p9381 (1500.0000)
SI Mtn rp t_mon P2
500.00 ... 1000000.00 [ms]
p9383 (10000.00)
STOP F --> STOP B
&
Actual value speed < p9360/p9560