List of Parameters
Parameters
1-335
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Description: Sets the behavior of safety functions and their feedback during pulse suppression in encoderless operation.
Dependency: Refer to: C01711
Note: SDI: Safe Direction (safe motion direction)
SSM: Safe Speed Monitor (safety-relevant feedback signal from the velocity monitoring)
Re bit 00:
For bit = 1 and with the SSM safety function activated, the following applies:
- During pulse suppression, monitoring is switched off and the feedback signal has a 0 signal level.
For bit = 0 and with the SSM safety function activated, the following applies:
- Monitoring continues during pulse suppression. The feedback signal last displayed before pulse suppression is
kept and the system goes into the STO state.
Re bit 08:
For bit = 1 and with the SDI safety function activated, the following applies:
- During pulse suppression, monitoring is switched off and the status signal indicates inactive.
For bit = 0 and with the SDI safety function activated, the following applies:
- Monitoring continues during pulse suppression. The status signal indicates active and the system goes into the
STO state.
Description: Sets the behavior of safety functions and their feedback during pulse suppression in encoderless operation.
Dependency: Refer to: C01711
Note: SDI: Safe Direction (safe motion direction)
SSM: Safe Speed Monitor (safety-relevant feedback signal from the velocity monitoring)
Re bit 00:
For bit = 1 and with the SSM safety function activated, the following applies:
- During pulse suppression, monitoring is switched off and the feedback signal has a 0 signal level.
For bit = 0 and with the SSM safety function activated, the following applies:
- Monitoring continues during pulse suppression. The feedback signal last displayed before pulse suppression is
kept and the system goes into the STO state.
Re bit 08:
For bit = 1 and with the SDI safety function activated, the following applies:
- During pulse suppression, monitoring is switched off and the status signal indicates inactive.
For bit = 0 and with the SDI safety function activated, the following applies:
- Monitoring continues during pulse suppression. The status signal indicates active and the system goes into the
STO state.
p9309 SI Motion behavior during pulse suppression (processor 2) / SI Mtn behav IL P2
PM240
PM250
PM260
CU240E-2 DP F
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: C(95) Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - 0000 0000 1111 1111 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 SSM during pulse suppression and sensor-
less
Becomes inactive Remains active -
08 SDI during pulse suppression and sensor-
less
Becomes inactive Remains active -
p9309 SI Motion behavior during pulse suppression (processor 2) / SI Mtn behav IL P2
PM240
PM250
PM260
CU240E-2 F
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: C(95) Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - 0000 0000 1111 1111 bin
Bit field: Bit Signal name 1 signal 0 signal FP
08 SDI during pulse suppression and sensor-
less
Becomes inactive Remains active -