Siemens SINAMICS G120 - p2257 Technology controller, ramp-up time; Tec_ctrl t_ramp­up; p2258 Technology controller ramp-down time; Tec_ctrl t_ramp­dn; r2260 CO: Technology controller setpoint after ramp-function generator; Tec_ctr set aftRFG; p2261 Technology controller setpoint filter time constant; Tec_ctrl set T

Siemens SINAMICS G120
750 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of Parameters
Parameters
1-307
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Description: Sets the ramp-up time of the technology controller.
Dependency: Refer to: p2258
Note: The ramp-up time is referred to 100 %.
Description: Sets the ramp-down time of the technology controller.
Dependency: Refer to: p2257
Note: The ramp-down time is referred to 100 %.
Description: Sets the setpoint after the ramp-function generator of the technology controller.
Description: Sets the time constant for the setpoint filter (PT1) of the technology controller.
Description: Displays the smoothed setpoint after the setpoint filter (PT1) of the technology controller.
p2257 Technology controller, ramp-up time / Tec_ctrl t_ramp-up
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0.00 [s] 650.00 [s] 1.00 [s]
p2258 Technology controller ramp-down time / Tec_ctrl t_ramp-dn
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0.00 [s] 650.00 [s] 1.00 [s]
r2260 CO: Technology controller setpoint after ramp-function generator /
Tec_ctr set aftRFG
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Data set: -
Units group: 9_1 Unit selection: p0595
Min Max Factory setting
- [%] - [%] - [%]
p2261 Technology controller setpoint filter time constant / Tec_ctrl set T
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0.000 [s] 60.000 [s] 0.000 [s]
r2262 CO: Technology controller setpoint after filter / Tec_ctr set aftFlt
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Data set: -
Units group: 9_1 Unit selection: p0595
Min Max Factory setting
- [%] - [%] - [%]