List of Parameters
Parameters
1-109
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Description: Sets the signal source to block the master control.
Dependency: Refer to: r0807
Note: The commissioning software (drive control panel) uses the master control.
Description: Displays what has the master control.
The drive can be controlled via the BICO interconnection or from external (e.g. the commissioning software).
Dependency: Refer to: p0806
Notice: The master control only influences control word 1 and speed setpoint 1. Other control words/setpoints can be trans-
ferred from another automation device.
Note: Bit 0 = 0: BICO interconnection active
Bit 0 = 1: Master control for PC/OP
The master control is used from the commissioning software (drive control panel) and from the Operator Panel (OP,
LOCAL mode).
Description: Copies one Command Data Set (CDS) into another.
Index: [0] = Source Command Data Set
[1] = Target Command Data Set
[2] = Start copying procedure
Dependency: Refer to: r3996
Notice: When the command data sets are copied, short-term communication interruptions may occur.
Note: Procedure:
1. In Index 0, enter which command data set should be copied.
2. In Index 1, enter the command data set that is to be copied into.
3. Start copying: Set index 2 from 0 to 1.
p0809[2] is automatically set to 0 when copying is completed.
p0806 BI: Inhibit master control / PcCtrl inhibit
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - 0
r0807.0 BO: Master control active / PcCtrl active
Access level: 3 Calculated: - Data type: Unsigned8
Can be changed: - Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Master control active Yes No 5030,
6031
p0809[0...2] Copy Command Data Set CDS / Copy CDS
Access level: 2 Calculated: - Data type: Unsigned8
Can be changed: T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0 3 0