Parameters
List of Parameters
1-356
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Description: Displays the status of the acceptance test mode.
Value: 0: [00 hex] Acc_mode inactive
12: [0C hex] Acc_mode not possible due to POWER ON fault
13: [0D hex] Acc_mode not possible due to incorrect ID in p9570
15: [0F hex] Acc_mode not possible due to expired Acc_timer
172: [AC hex] Acc_mode active
Dependency: Refer to: p9558, p9570
Refer to: C01799
Description: Sets the reference value to define the brake ramp.
The rate of rise of the brake ramp depends upon p9581 (reference value) and p9583 (monitoring time).
Dependency: Refer to: p9582, p9583
Description: Sets the delay time for monitoring the brake ramp.
Monitoring of the brake ramp starts once the delay time has elapsed.
Dependency: Refer to: p9581, p9583
Description: Sets the monitoring time to define the brake ramp.
The rate of rise of the brake ramp depends upon p9581 (reference value) and p9583 (monitoring time).
Dependency: Refer to: p9581, p9582
r9571 SI Motion acceptance test status (processor 1) / SI Mtn acc_status
CU240E-2 DP F
CU240E-2 F
Access level: 3 Calculated: - Data type: Integer16
Can be changed: - Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0000 hex 00AC hex -
p9581 SI Motion brake ramp reference value (processor 1) / SI Mtn ramp ref P1
CU240E-2 DP F
CU240E-2 F
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: C(95) Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
600.0000 [rpm] 24000.0000 [rpm] 1500.0000 [rpm]
p9582 SI Motion brake ramp delay time (processor 1) / SI Mtn ramp t P1
CU240E-2 DP F
CU240E-2 F
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: C(95) Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
10.00 [ms] 99000.00 [ms] 250.00 [ms]
p9583 SI Motion brake ramp monitoring time (processor 1) / SI Mtn rp t_mon P1
CU240E-2 DP F
CU240E-2 F
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: C(95) Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0.50 [s] 1000.00 [s] 10.00 [s]