EasyManua.ls Logo

Siemens SINAMICS G120 - Fig. 2-61 2804 - Basic Functions, Status words

Siemens SINAMICS G120
750 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Function diagrams
Safety Integrated
2-562
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Fig. 2-61 2804 – Basic Functions, Status words
- 2804 -
Function diagram
87654321
FP_2804_97_63.vsd
Safety Integrated
G120 CU240E-2 <**>
13.12.2010 V4.4
Basic Functions, Status words
1
9
10
...
15
0[2810.3]
[2810.7]
[2802.5]
[2802.8]
1
0
0
31[2810.5]
[2802.7]
...
...
SI status P1
r9772
r9772
SI general fct P1
r9771
Status word Safety Integrated
Processor 1
Bit No.
1 = STO selected on Processor 1
1 = STO active on Processor 1
Reserved
1 = STOP A cannot be acknowledged, active
Functions available on Processor 1 und
Processor 2
1 = STOP A active
Reserved
1 = STOP F active
Bit No.
Bit No.
Reserved
Status word Safety Integrated
Processor 1 and Processor 2
Functions available on Processor 1 und
Processor 2
1 = STO supported via terminals
1 = STO selected in drive
1 = STO active in drive
1 = The shutdown paths must be tested
17
18
16
19
20
1 = STO cause: Safety commissioning mode
1 = STO cause: selection via terminal
Reserved
1 = STO cause: missing actual value
1 = STO cause: selection PROFIsafe
SI status P1+P2
r9773
r9773
6
1 = PROFIsafe supported
...
Reserved
...
Reserved
[2810.3]
<**> Valid for all CU240E-2 variants
1
...
0[2810.3] &
&[2810.6]
SI Status P2
r9872
r9872
Bit No.
Reserved
Status word Safety Integrated
Processor2
1 = STO selected on Processor 2
1 = STO active on Processor 2
Status (Processor 1 + Processor 2)Status (Processor 2)Status (Processor 1)
<1>
only PROFIBUS variants
<1>