Siemens SINAMICS G120 - p1048[0...n] Motorized potentiometer ramp-down time; Mop ramp­down time; r1050 CO: Motor. potentiometer setpoint after the ramp-function generator; Mop setp after RFG; p1051[0...n] CI: Speed limit RFG positive direction of rotation; n_limit RFG pos; p1052[0...n] CI: Speed limit RFG negative direction of rotation; n_limit RFG neg

Siemens SINAMICS G120
750 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of Parameters
Parameters
1-143
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Description: Sets the ramp-down time for the internal ramp-function generator for the motorized potentiometer.
The setpoint is changed from the speed/velocity limit (p1082) to zero within this time (if no initial rounding-off has
been activated).
Dependency: Refer to: p1030, p1047, p1082
Note: The deceleration time is extended corresponding to the activated initial rounding-off (p1030.2).
Description: Sets the effective setpoint after the internal motorized potentiometer ramp-function generator.
This setpoint is the output value of the motorized potentiometer and must be appropriately interconnected onwards
(e.g. with the main setpoint).
Dependency: Refer to: p1070
Note: For "With ramp-function generator", after an OFF1, OFF2, OFF3 or for a 0 signal via BI: p0852 (inhibit operation,
cancel pulses) the ramp-function generator output (r1050) is set to the starting value (configuration via p1030.0).
Description: Sets the signal source for the speed limit of the positive direction on the ramp-function generator input.
Description: Sets the signal source for the speed limit of the positive direction on the ramp-function generator input.
Description: Sets the signal source for the speed limit of the negative direction on the ramp-function generator input.
p1048[0...n] Motorized potentiometer ramp-down time / Mop ramp-down time
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: - Unit selection: -
Min Max Factory setting
0.000 [s] 1000.000 [s] 10.000 [s]
r1050 CO: Motor. potentiometer setpoint after the ramp-function generator /
Mop setp after RFG
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2000 Data set: -
Units group: 3_1 Unit selection: p0505
Min Max Factory setting
- [rpm] - [rpm] - [rpm]
p1051[0...n] CI: Speed limit RFG positive direction of rotation / n_limit RFG pos
CU240B-2
CU240B-2 DP
CU240E-2
CU240E-2 DP
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: p2000 Data set: CDS, p0170
Units group: - Unit selection: -
Min Max Factory setting
- - 1083[0]
p1051[0...n] CI: Speed limit RFG positive direction of rotation / n_limit RFG pos
CU240E-2 DP F
CU240E-2 F
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: p2000 Data set: CDS, p0170
Units group: - Unit selection: -
Min Max Factory setting
- - 9733[0]
p1052[0...n] CI: Speed limit RFG negative direction of rotation / n_limit RFG neg
CU240B-2
CU240B-2 DP
CU240E-2
CU240E-2 DP
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: p2000 Data set: CDS, p0170
Units group: - Unit selection: -
Min Max Factory setting
- - 1086[0]