Siemens SINAMICS G120 - p1758[0...n] Motor model changeover delay time closed;open-loop control; MotMod t cl_op; p1759[0...n] Motor model changeover delay time open;closed-loop control; MotMod t op_cl; r1762[0...1] Motor model deviation component 1; MotMod dev comp 1; r1763 Motor model deviation component 2; MotMod dev comp 2

Siemens SINAMICS G120
750 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of Parameters
Parameters
1-229
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Description: Sets the minimum time for falling below the changeover speed when changing from closed-loop controlled opera-
tion to open-loop controlled operation.
Dependency: Refer to: p1755, p1756
Description: Sets the minimum time for exceeding the changeover speed when changing from open-loop controlled operation to
closed-loop controlled operation.
Dependency: Refer to: p1755, p1756
Note: When p1759 = 2000 ms, the delay time becomes ineffective and the model changeover is determined by the output
frequency only.
Description: Induction motor (ASM):
Displays the referred imaginary system deviation for the adaptation circuit of the motor model.
Permanent-magnet synchronous motor (PESM):
Displays the system deviation for speed adaptation.
r1762.0: Angular deviation [rad-el] of the estimated EMF.
r1762.1: Angular deviation [electr. deg.] of the low-level signal response for pulse technique.
Index: [0] = Deviation Model1
[1] = Deviation Model2
Description: Induction motor (ASM):
Displays the referred real system deviation for the adaptation circuit of the motor model.
Permanent-magnet synchronous motor (PESM):
Not used.
p1758[0...n] Motor model changeover delay time closed/open-loop control / MotMod t cl_op
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: - Unit selection: -
Min Max Factory setting
100 [ms] 10000 [ms] 500 [ms]
p1759[0...n] Motor model changeover delay time open/closed-loop control / MotMod t op_cl
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: - Unit selection: -
Min Max Factory setting
0 [ms] 2000 [ms] 0 [ms]
r1762[0...1] Motor model deviation component 1 / MotMod dev comp 1
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - -
r1763 Motor model deviation component 2 / MotMod dev comp 2
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - -