Siemens SINAMICS G120 - r2197.0...13 CO;BO: Status word monitoring 1; ZSW monitor 1

Siemens SINAMICS G120
750 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters
List of Parameters
1-296
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Description: Displays the first status word for monitoring functions.
Notice: Re bit 06:
When the overspeed is reached, this bit is set and F07901 output immediately following this. The bit is canceled
again as soon as the next pulse inhibit is present.
Note: Re bit 00:
The threshold value is set in p1080 and the hysteresis in p2150.
Re bit 01, 02:
The threshold value is set in p2155 and the hysteresis in p2140.
Re bit 03:
1 signal direction of rotation positive.
0 signal: direction of rotation negative.
The hysteresis is set in p2150.
Re bit 04:
The threshold value is set in r1119 and the hysteresis in p2150.
Re bit 05:
The threshold value is set in p1266 and the delay time in p1228.
Re bit 06:
The hysteresis is set in p2162.
Re bit 07:
The threshold value is set in p2163 and the hysteresis is set in p2164.
Re bit 08:
The threshold value is set in p2170 and the delay time in p2171.
Re bit 09, 10:
The threshold value is set in p2172 and the delay time in p2173.
Re bit 11:
The threshold value is set in p2179 and the delay time in p2180.
Re bit 12:
The threshold value is set in p2182, the hysteresis in p2162, and the delay time (for canceling the signal) in p2152.
r2197.0...13 CO/BO: Status word monitoring 1 / ZSW monitor 1
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 |n_act| <= n_min p1080 Yes No 8020
01 -
02 -
03 n_act >= 0 Yes No 8011
04 |n_act| >= n_set Yes No 8020
05 |n_act| <= n_standstill p1226 Yes No 8020
06 |n_act| > n_max Yes No 8010
07 Speed setp - act val deviation in tolerance
t_off
Yes No 8011
08 I_act >= I_threshold value p2170 Yes No 8020
09 Vdc_act <= Vdc_threshold value p2172 Yes No 8020
10 Vdc_act > Vdc_threshold value p2172 Yes No 8020
11 Output load is not present Yes No 8020
12 |n_act| > n_max (delayed) Yes No 8021
13 |n_act| > n_max error Yes No -