Chapter 2 TL1 Reference
Retrieve Phase Build-Out Parameters
102 SSU-2000 Technical Reference 12713020-003-2 Revision F.01 – January 2007
Retrieve Phase Build-Out Parameters
This command returns the Phase Build-Out (PBO) settings for the SSU-2000. All
Input modules use this setting.
Syntax
RTRV-PRMTR-PBO:[tid]::ctag;
Response Format
^^^"aid:mode" <cr lf>
where:
aid = ALL
mode = [DIS | EVT | REP | NONE]
where:
DIS indicates the PBO function has been disabled.
EVT indicates the PBO function is enabled. PBO events are displayed and stored
in the COMM module event buffer.
REP indicates the PBO function is enabled.
PBO events are displayed, but the event is not stored in the COMM module event
buffer.
NONE indicates the PBO function is enabled. The PBO event is neither displayed
nor stored in the COMM module event buffer.
Related Commands
Set Phase Build-Out Parameter, on page 169