Chapter 4 NTP and SNMP
SNMP Protocol
266 SSU-2000 Technical Reference 12713020-003-2 Revision F.01 – January 2007
ICS:SNMP [DISABLE|ENABLE]
Add/delete the SNMP manager IP address for traps (up to four managers in the
SNMP manager table)
TL1:
SET-PRMTR-SNMP-MANAGER:[tid]::ctag::mode,[ip];
and
RTRV-PRMTR-SNMP-MANAGER:[tid]::ctag;
ICS:SNMP TRAP {ALARM|ALL}
Keep-Alive Support
SNMP supports a "keep-alive" mode based on a user-settable time. An event is
generated to alert the upstream support system that the SSU-2000 and associated
paths are functional. This mode is only supported in TL1 and SNMP sessions, not in
ICS, Telnet, or Hyperterminal sessions. The factory default mode is set to Disabled.
TL1:
SET-PRMTR-KEEPALIVE:[tid]::ctag::[tl1_time], [snmp_time];
and
KEEPALIVE:[tid]::ctag;
ICS: KEEPALIVE [TL1|SNMP] [time]
Shelf Information
Each shelf and distribution unit’s description, part number, and revision level can be
displayed. Using the following commands with specific options the hardware
information can be displayed. Refer to Retrieve Inventory, on page 75, and
CONFIG, on page 199, for more information.
TL1:
RTRV-INV:[tid]:[aid]:ctag;
ICS: CONFIG xAy {REMOVE|DISABLE|ENABLE}
Software Information
Individual module software, part number, and associated revision level can be
displayed. Using the following commands with specific options the software
information can be displayed. Refer to Retrieve Inventory, on page 75, and
CONFIG, on page 199, for more information.
TL1:
RTRV-INV:[tid]:[aid]:ctag;
ICS:CONFIG SW